How many dB of insulation does an office need?

The Polish standard PN-B-02151, EU requirements and real-world practice. How to match a partition system to the noise level and legal requirements.

What does sound insulation measure?

The sound insulation of a partition (wall, partition, door) is measured with the Rw index (laboratory) or DnTw (in situ). It expresses by how many decibels the sound passing from one side of the partition to the other is reduced. A higher index means better insulation. In-situ values are usually 2–5 dB lower than laboratory ones because of flanking (sound passing sideways through the ceiling, floor and neighbouring partitions).

Standard PN-B-02151-3

The Polish standard PN-B-02151-3:2015 sets minimum requirements for internal partitions:

  • Walls between offices (one person or a small company): R'w ≥ 35 dB
  • Walls between a conference room and an office: R'w ≥ 45 dB
  • Walls next to loud rooms (call centre, production): R'w ≥ 50 dB
  • Doors to private offices and meeting rooms: R'w ≥ 30 dB

It is worth noting that the standard applies to new buildings or after a major renovation. In practice, many offices operate below these requirements, especially when partitions were installed without an acoustic design.

What do partition systems deliver?

The insulation of office partition systems differs significantly depending on their construction:

  • Desk dividers (Soft and similar): Rw < 15 dB. They are not designed for insulation.
  • System 20, 32 mm upholstered infill: Rw ≈ 25–30 dB. For creating zones.
  • System 32, 52 mm upholstered infill: Rw ≈ 38–42 dB. Meets the standard for offices.
  • System 32, 10 mm VSG laminated glass: Rw ≈ 40–44 dB. Close to upholstery.
  • Double partition with an air gap: Rw ≈ 50–55 dB. For extreme requirements.

Important: these values apply to the partition alone, without openings, without gaps under the partition and without flanking. In reality, every leaky joint reduces insulation by 5–15 dB.

How to calculate the insulation you need?

The starting noise level in a call centre is 70–80 dB. The permitted noise level in offices for mental work is 55 dB. Insulation needed: 80 - 55 = 25 dB. Add a margin for flanking and leaks: +10 dB. Required partition insulation: 35 dB. System 32 with upholstery meets this requirement with room to spare.

For a typical open-plan office (noise level 65 dB) and a private office (target 45 dB): 65 - 45 + 10 = 30 dB. System 20 or even System 32 in a simplified configuration is enough here.

Flanking: the overlooked factor

Flanking is sound passing "around" a partition: through a suspended ceiling, a raised floor or neighbouring walls. In offices with a system ceiling, sound passes freely over the partitions unless acoustic inserts are used. A good partition without a sealed ceiling loses 10–20 dB of effective insulation. That is why conference room projects with high requirements always include ceiling insulation, not just the partitions.